Permits - Permit# SP-2021-00065 - 4681 Shoreline Drive - 7/8/2021City of Spring Park Permit
1C11'YOF
Permit Number: SP-2021-00065
Issue Date: 7/8/2021
Zoning Type: COMMERCIAL
Use Type:
To Schedule an Inspection Call: 952-442-7520
24 HOUR NOTICE REQUIRED FOR ALL INSPECTIONS ♦ MON-FRI: 8AM-4:30PM ♦ NO HOLIDAYS
Details
Site Address: 4681 SHORELINE DRIVE, SP, MN 55384
Description:
1 Replacement RTU
Permit Granted To: Guardian Mechanical Service Inc
Homeowner's Name: 5TH STREET VENTURES LLC
Phone Number:
Parcel #: 1811723330049
Fees
12991 State Surcharge
12991 Permit Fee - PLG, MECH Comm
12991 Plan Review Fee
Notes
Permit Type: MECH - General (Comm)
Permit Exp: 12/28/2021
Valuation: $13,400.00
7/1/2021
1.00
7/8/2021
7/1/2021
1.00
7/8/2021
7/1/2021
1.00
7/8/2021
Paid $6.70
Paid $315.50
Paid $205.08
Total: $527.28
• This permit is issued in accordance with and subject to all provisions of Ordinances and policies governing building and zoning in City of
Spring Park.
• Permit Holder/Contractor/Owners Agent is responsible to call for the inspections!
• Permit Packet, including approved plan, and this inspection record must be posted in an accessible location before calling for inspection.
Maintain this inspection record until work is complete.
• No deviations from the approved plans are allowed without prior consent from the building inspections department.
• To Owner, Occupant, or Contractor: It is ILLEGAL TO OCCUPY this area/building until all required final inspections have been made,
approved, signed, and certificate of occupancy issued!
Scott Qualle, Building Official
City of Spring Park #4349 Warren Avenue ♦ 55384 Copyright 02021
INSPECTION RECORD
2020 MN State Building Code
City of Spring Park Permit Number: SP-2021-00065 Issue Date: 7 8 2021
SITE ADDRESS: 4681 SHORELINE DRIVE, SP, MN 55384 Description:
PERMIT TYPE: MECH - General (Comm) 1 Replacement RTU
ZONE/USE TYPE: COMMERCIAL
APPLICANT: Guardian Mechanical Service Inc
OWNER: STH STREET VENTURES LLC
No inspection will be performed, and a re -inspection fee will be charged, if this "Inspection Record", the "City of Spring Park Permit", and, when applicable, the
approved plans are not available to the inspector. This permit expires if construction activity does not commence within 180 days from obtaining this permit; when
construction activity has been suspended or abandoned for at least 180 days; or the work has not been inspected within 180 days from the last documented activity.
IF SEPARATE PERMITS ARE REQUIRED, REFER TO THE "SEPARATE PERMITS REQUIRED FOR:" STAMP ON YOUR APPROVED
PLANS/CONSTRUCTION DOCUMENTS TO IDENTIFY WHAT SEPARATE PERMITS ARE REQUIRED.
ALL REQUIRED ROUGH -IN INSPECTIONS, NOTED ON SEPARATE PERMITS, MUST BE COMPLETED PRIOR TO SCHEDULING A FRAMING
INSPECTION.
ALL REQUIRED FINAL INSPECTIONS, NOTED ON SEPARATE PERMITS, MUST BE COMPLETED PRIOR TO SCHEDULING A BUILDING FINAL
INSPECTION.
DO NOT COVER ITEMS TO BE INSPECTED.
Permit Card (8)
Inspection Inspector's Response Approval Date Comments or Corrections Required
Fire Dept Requirements Met Required
Gas Line Installation & Air Test Required
Duct Insulation Required
Balance Report(s) Required
Startup Report(s) Required
Mechanical Rough -In Required
Gas Line Air Test Required
Mechanical Final Required
MUST CALL TO SCHEDULE NO LATER THAN THE BUSINESS DAY PRIOR TO THE INSPECTION DAY: 8:00 A.M. TO 4:30 P.M. MONDAY THRU
FRIDAY. PHONE NUMBER TO CALL: 952-"2-7520
When a Certificate of Occupancy is needed, return this card and the approved final inspection notice to
the City of Spring Park office.
6/24/2021
20210623_223418.jpg
±- x*s- '` '`', �.. 'ram, i` k p { k
Wy
City'oft i ngP rig IC y # g I
-4349
�pringPalk,Mt55384., . p`
City 92=4719t?51 11IINSPECT: 952-4A2 7520
Perrfti Ntmbew, `.SP 2021 0065
Job Address%$1_ SW.�wKc �fi.. Owner's Phone
Owner's Name as v t-r lBusiness Name'z��wi.S-i'1tr.p►.
s.� --
Owner's Address lM1 N, 3atga3&W gw- Tj- 4= City/State/zlplcAwm
Mechanical ContractotGuulblw l"lP. WfJkt AL UMCV. Phone (of
i• �eel� -A 12
Addresslul So. city/state/z(pCdMLrk-CtAvti,t 0 5S66
State Bond No. Mt,-j Gas Fitters License No.7.0k%00QQ" yq
CHECK TYPE OF WORK: ❑ New Construction ❑ Addition 0 Alteration Replacement
Furnace
Air Cond
In Floor Heat
Air Exch
Fireplace
Exhaust Fan
Boiler
Wall Neater
'1,
Rooftop Unit
Unit Heater
Range Hood
Make -Up Air
Equipment Efficiency
System
Tag(s)
Mfg. &
Model
No.
Equipment
Type
Heating
Cooling
Rated
Capacity
Rated
Efficiency
Minimum
Efficiency
Rated
Capacity
Rated
Efficiency
Minimum
Efficiency
Econ. Min..
Efficien
+
RTLk
1.5
`IS D
VALUATION OF WORK $13.400 VALUATION APPROVED $ 13,y00
I hereby certify that l have read and examined this. application and know the same to be true and correct. All provisions of laws and
ordinances governing this type of work will be compiled with whether specified herein or not. The granting of a permit does not presume
to give authority to violate or cancel the provisions of any other state or local law regulating construction or the performance of
construction: I agree to pay all plan review fees even if I choose not proceed with the work. 1 certlfyall taxes and Municipal fees owed
in connection with this pro rty are current.
(3_�% LZd7-
Ap icant's Signature Date
OFFICE USE ONLY
Permit Fee ........................... 3 115.50 Plans checked by:
Code Review ....................... 20508
State Surcharge..... .......... _670
Other ......... Date;
................... 6130/2021
Total Permit Charge; $ 527.28
https://maiI.googIe.com/mail/u/1 /#inbox/FMfcgzGkXwGgQtJSgJfbpDMrjpwXLgCP?projector=1 &messagePartld=0.3 1 /1
Thank you for your Payment!
Transaction ID:12991
Transaction Number:
Transaction Type: Payment
Recipient: Contractor
Notes:
Fees
Plan Review Fee
State Surcharge
Permit Fee - PLG, MECH Comm
1CIIYOF
k �� Cj,rlvri-\ rk K
City of Spring Park
4349 Warren Avenue
SP MN,55384
Ph:952-442-7520
$527.28
Date: 7/8/2021
Method:
Address: 4681 SHORELINE DRIVE, SP, MN 55384
Reference: Permit Number: SP-2021-00065 Type: MECH - General
(Comm) for Guardian Mechanical Service Inc
Paid
1.00
$205.08
Paid
1.00
$6.70
Paid
1.00
$315.50
$205.08
$6.70
$315.50
Total Amount: $527.28
Page 1 of 1 Printed on: 7/8/2021
Payment Confirmation
Payer Information:
Payment Made By:
Payment Made For:
Email:
Address:
Payment Description
Payment Date:
Joseph Dragich
Guardian Mechanical Service Inc.
Admin@guardmech.com
8821 Hamlet Ave. So.
Cottage Grove, MN 55016
Permits
7/6/2021 6:40:21 PM
Business Name Payment Payment Confirmation Amount Convenience Total
Method Account Number Fee
City of Spring Park VISA ****2390 55188267 $527.28 $15.55 $542.83
(Permits)
This notice confirms that the above payment was successfully submitted to our payment processor, PSN,
and is currently being processed. Thank you for using PSN.
NOTE: While credit and debit cards generally are immediately approved, the transaction is not considered
"paid" until the credit or debit card company has "settled" the payment which occurs most often within 24
hours. If there are any issues with your payment, PSN will send an email to the address you provided. To
check on the progress of your payment, you can log into your profile. Thanks for using PSN.
Contact Us
PSN Customer Support Submit your question and get a response within one business day.
Payment Processing Powered by Payment Service Network (PSN)
THIS COMMUNICATION IS INTENDED ONLY FOR THE ADDRESSEE(S) AND MAY CONTAIN INFORMATION THAT IS PRIVILEGED AND CONFIDENTIAL.
YOU ARE HEREBY NOTIFIED THAT, IF YOU ARE NOT AN INTENDED RECIPIENT LISTED ABOVE, OR AN AUTHORIZED EMPLOYEE, OR AGENT OF AN
ADDRESSEE OF THIS COMMUNICATION RESPONSIBLE FOR DELIVERING E-MAIL MESSAGES TO AN INTENDED RECIPIENT, ANY DISSEMINATION,
DISTRIBUTION, OR REPRODUCTION OF THIS COMMUNICATION (INCLUDING ANY ATTACHMENTS HERETO) IS STRICTLY PROHIBITED. IF YOU HAVE
RECEIVED THIS COMMUNICATION IN ERROR, PLEASE NOTIFY US IMMEDIATELY BY A REPLY E-MAIL ADDRESSED TO THE SENDER AND
PERMANENTLY DELETE THE ORIGINAL E-MAIL COMMUNICATION AND ANY ATTACHMENTS FROM ALL STORAGE DEVICES WITHOUT MAKING OR
OTHERWISE RETAINING A COPY.
The field copy of these plans must
be kept on -site and made
available to inspector during all
inspections.
To schedule inspections call
(952) 442-7520
Please have the permit number
and street address ready at the
time of the call.
Electrical
All electrical must be approved by local
Electrical Inspector.
For electrical permit inquiries please
contact the City of Spring Park Electrical
Inspector.
Dave Hucky
(952) 442-7520
Read all attached materials.
Everyone performing work
to which the code is
applicable shall comply
with the code.
Reviewed for Code Compliance
This review is limited to the submitted scope of work, is based upon the supposition that the plan
accurately depicts the intended construction and end -use, that the necessary legal authority has
been obtained to construct the project and work is subject to code compliance and field
inspection during construction.
By: nkastern
Date: 6/30/2021
Permit #: SP-2021-00065
Type of Construction:
Occupancy Classification: B
Code Edition: 2020 MBC
6/24/2021
20210623_223743.jpg
V
'ot+N.m,! Y11CMI3RHA0000 - " .y _
ih r a f
Trane Precedent Gas/Electric Packaged Rooftop
Applicntlon Unk SlyExtornal
iMi e,
DX
0008ng, 7.5 Ton Dual Alfftw Pressure� WkM Lerlgt l AANIMrMdt1 AAaMam
g. Compresw
Unit Features
Fresh Air Sehictlon WNW (rash eM s0ec8on
SupplyFenlDrlve/ Motor7ype Standard drive moles
pensislFlken Standard condenser ooil
Vokagelphaselhertz 208-230/60/3
2018-01-04 06:20:36Z Pop 1 0110
https://mail.google.com/mail/u/1/#inbox?projector=l 1/1
6/24/2021 20210623_223453.jpg
% t7-
s
L
Heating, Air Conditioning & Ventilation
t
Required Permit Submittals — please call the Building Inspection Department if you have any quesoiifs
regarding the submittal documents 9S2-442-7S20: 2 }
❑ MECHANICAL PERMIT
❑ Completed permit application including:
❑ Date
❑ Site Address
❑ Owner
❑ Owner Address
❑ Telephone Number
❑ Contractor Information (if'applicable)
❑ Description of work being performed
❑ Valuation of work being performed
❑ Signature of applicant
❑ Copy of signed contract (with price)
❑ 2 (two) sets of Signed Mechanical Plans including legend or symbol description
❑ 2 (two) sets of gas piping plans: Include layout, lengths, pipe sizing, valve locations, regulator locations, each unit BTU,
material type, operating pressure, pressure drop.
❑ Calculations: Provide heat loss/gain and indoor air quality ventilation calculations.
❑ Appliance Specification Sheets
❑ Complete and provide HVAC compliance forms for compliance with the Minnesota State Energy Code. The compliance
forms must correspond with the energy code option designated on the building permit.
Fees Required: The Building Code Department, before issuing any permit for the construction, installation,
alteration, or repair of any furnace, boiler, heating or power plant or system, or any device or equipment
connected therewith, or for any other device connected to, or to be connected with, any chimney or stack,
or for the construction, installation, alteration, addition or repair of any cooling piping and equipment, or of
any air conditioning system or ventilation system, or sheet metal duct work or equipment therewith, or of
any refrigeration plant or equipment, shall require the payment by the applicant for such permit fee, code
review fee, and state surcharge.
https://mail.google.com/mail/u/1/#inbox/FMfcgzGkXwGgQtJSgJfbpDMrjpwXLgCP?projector=1&messagePartld=0.2 1/1
6/24/2021
20210623_223510.jpg
'GENERAL (21t4)i8)
Model:
Unit Operating Voltage:
Unit Primary Voltage
Unit Secondary Vintage
Unit H adz.
U nil P ha se:
EER
Standard Motor
MCA
MFS:
MCB:
INDOOR MOTOR
Standard Motor
Number.
1
Horse power.
2.75
Motor Speed (RPM):
_
Phase
3
Full Load Amps
7.3
Loc;edRotorAmpt
_
COMPRESSOR Circuit IQ
Number.
2
Horsepower.
4I12.4
Phase:
3
Rated Load Amps:
15,91100
Locked Rotor Amps:
I io.w 1.0
YMC092F
OtrermadMoD
187-253
MCA: WA
208
MFS: NIA
230
►ACB: NIA
60
3
424
501
50.0
� w�aw r.�[M •n.n�.
N EATING -GENERAL 0
H selling Model
Homing Input (BTU1
Heating 0u1put (BTU)!
No. Bumers:
No. Stages
Field Installed Oversized M otor Gas Inim Pressure
MCA NIA NUuralGas(MINMsx):
MFS: NIA LP (lAInIMax)
MCB: NIA Gar Pipe Connection Site
Oversized Motor
Number.
NIA
Horsepower.
MIA
Motor Speed (RPM )
NIA
Phase
NIA
Full Load Amps:
NIA
LocitedRotorAmpt
NIA
ATA
Nigh
200,000I14000
i;B0000rnz,o0o
4
2
4.5H 4
11.0114.0
314'
Field Installed OverUzedUutw
Number. NIA
Horsepower. NIA
MotorSpeed(RPMX N/A
Phase NIA
Full Load Amps: NIA
Locked RotorAmps: NIA
OUTDOOR MOTOR
Number. 1
H orsepower. 0-75
M oto r Speed (RP td ): 1100
Phase: 1
Full Load Amps: 4.0
Locked Rotor Amps: 9.3
POWER EXHAUST ACCESSORY (3f FILTERS REFRIGERANT (2)
(Field Installed PowerE)Maust) Type R-410
Phase: ei/A. Type Throwaway Fa dory Cherge
Hcrsepover. It1A Fumished: Yes
IdctorSpeed (RP1.1): It/A Number 4 Circuital S.Sb
Full Load Amps. NIA Recommended 20'x25'k2" Circuit02 4.2b
Locked Rotor Amps: NIA
hftps:Hmail.google.com/mail/u/1/#inbox/FMfcgzGkXwGgQtJSgJfbpDMrjpwXLgCP?projector=l &messagePartld=0.l 1 /1
OUTDOOR MOTOR
Number. 1
H orsepower. 0-75
M oto r Speed (RP td ): 1100
Phase: 1
Full Load Amps: 4.0
Locked Rotor Amps: 9.3
POWER EXHAUST ACCESSORY (3f FILTERS REFRIGERANT (2)
(Field Installed PowerE)Maust) Type R-410
Phase: ei/A. Type Throwaway Fa dory Cherge
Hcrsepover. It1A Fumished: Yes
IdctorSpeed (RP1.1): It/A Number 4 Circuital S.Sb
Full Load Amps. NIA Recommended 20'x25'k2" Circuit02 4.2b
Locked Rotor Amps: NIA
hftps:Hmail.google.com/mail/u/1/#inbox/FMfcgzGkXwGgQtJSgJfbpDMrjpwXLgCP?projector=l &messagePartld=0.l 1 /1
POWER EXHAUST ACCESSORY (3f FILTERS REFRIGERANT (2)
(Field Installed PowerE)Maust) Type R-410
Phase: ei/A. Type Throwaway Fa dory Cherge
Hcrsepover. It1A Fumished: Yes
IdctorSpeed (RP1.1): It/A Number 4 Circuital S.Sb
Full Load Amps. NIA Recommended 20'x25'k2" Circuit02 4.2b
Locked Rotor Amps: NIA
hftps:Hmail.google.com/mail/u/1/#inbox/FMfcgzGkXwGgQtJSgJfbpDMrjpwXLgCP?projector=l &messagePartld=0.l 1 /1
hftps:Hmail.google.com/mail/u/1/#inbox/FMfcgzGkXwGgQtJSgJfbpDMrjpwXLgCP?projector=l &messagePartld=0.l 1 /1
SPRING PARK
On Lake ;v „newnk
June 30, 2021
File Number: SP-2021-00065
Project Location: Southwest Eye Care
4681 Shoreline Dr
Owner: 51h St Ventures LLC
102 Jonathan Blvd N #200
Chaska, MN 55318
Mechanical Contractor: Guardian Mechanical Services Inc.
8821 Hamlet Ave S.
Cottage Grove, MN 55016
Scope: Like -for -like replacement of one RTU.
Approval is based on the correction of all noted deficiencies and compliance with all items
listed below.
The plans and specifications, for the project named above, have been reviewed for substantial
compliance with the current Minnesota State Building Code. This review is limited to the
submitted scope of work; is based upon the supposition that the data on which the design is based
are correct; and that the necessary legal authority has been obtained to construct the project.
Although every attempt has been made to identify code issues or concerns for proper and
necessary change, the project designer(s), the building contractor(s) and the property owner(s)
are ultimately responsible for providing complete code compliance and maintaining minimum
construction standards for the safeguarding of life or limb, health, public welfare and property
while constructing this project.
The following comments are related to the approved plans and will be verified during the
construction process or is general information regarding code requirements, inspections, and/or
permits.
Items to be Addressed and/or Corrected:
1. Outside ventilation is required. Balance reports must show this minimum amount of OA
is supplied at all times the building is occupied. (MMC 401.2)
General Information:
1. Inspections:
a. All mechanical installations must be inspected and tested in accordance with the
requirements of the Minnesota State Mechanical and Fuel Gas Code.
b. It is the responsibility of the contractor/installer to notify the inspection department
when ready to schedule an inspection. Call the building inspection department at
(952) 442-7520 between the hours of 8:00 a.m. and 4:30 p.m., Monday through
Friday.
c. The approved permit and all related plans and documentation shall be on
site and available to the inspector at the time of inspection.
d. Failure to provide the required documentation to the inspector at the time of
inspection may result in a cancelation of the inspection and additional inspections
fees for the additional inspection(s).
e. The field inspector may identify additional code compliance requirements.
Any additional identified code compliance requirements shall be completed.
Required Inspections:
• Rough -in: Inspection of all materials installed prior to covering
• Gas Line Installation/Air Test
• Final with Manometer
Required Documentation:
• Mechanical systems shall be balanced to with 10% of the design
capacities. Provide a copy of the balance report(s) to the Building
Official for review and approval prior to the final mechanical
inspection. (MMC section 309.2)
• Provide copies of startup reports for each fuel fired appliance to the
Building Official for review and approval prior to the final mechanical
inspection.
2. Governing Codes:
• 2020 Minnesota Mechanical and Fuel Gas Code (MMC & MFGC) (MN Rule 1346)
➢ 2018 International Mechanical Code: Ch. 2-15 (IMC) as amended
➢ 2017 NFPA 96: Ch. 1-10 & 12-15 (NFPA) as amended
➢ 2018 International Fuel Gas Code: Ch. 2-8 (IFGC) as amended
• 2015 Minnesota Plumbing Code (MPC) (MN Rule 4714)
➢ 2012 Uniform Plumbing Code: Ch. 2-11, 14, 17 (UPC) as amended
• 2020 Minnesota Energy Code (MEC) (MN Rule 1322)
➢ 2018 International Energy Conservation Code: Residential provisions, Ch.
2-5 (IECC-RE) as amended
3. Comments:
a. Read all attached information.
b. Every person performing work for which the code is applicable shall comply with
the code requirements.
c. The person, firm, or organization securing the permit is responsible for code
compliance for the work being performed.
d. The site address shall be posted and visible from the fronting street.
4. Equipment Installation:
a. Equipment shall be installed as required by the terms of their approval, in accordance
with the conditions of the listing, the manufacturer's installation instructions and the
MN State Mechanical Code. Manufacturer's installation instructions shall be
available on the lob site at the time of inspection. (MMC section 304.1)
Page 2 of 5
b. Clearance around appliances shall be sufficient to allow inspection, service, repair or
replacement. (MMC section 306.1)
c. An unobstructed passage way measuring not less than 36 inches wide and 80 inches
in height shall be provided for appliances within rooms. (MMC section 306.2)
d. Mechanical ventilation systems shall be provided with manual or automatic controls
that will operate such systems whenever the spaces are occupied. Air-conditioning
systems that supply required ventilation air shall be provided with controls designed to
automatically maintain the required outdoor air supply rate during occupancy. (MMC
405.1)
5. Gas Piping:
a. Gas piping shall be sized in compliance with MFGC section 402.
b. Corrugated stainless steel tubing (CSST) gas piping systems shall be bonded to the
electrical service grounding electrode system with minimum 6 AWG copper wire of
equivalent. (MFGC section 310.1.1)
a. This section applies to corrugated stainless -steel tubing (CSST) that is listed
with an arc -resistant jacket or coating system in accordance with ANSI LC
1/CSA 6.26. The CSST shall be electrically continuous and bonded to an
effective ground fault current path. Where any CSST component of a piping
system does not have an arc -resistant jacket or coating system, the bonding
requirements of Section 310.2 shall apply. Arc -resistant -jacketed CSST shall
be considered to be bonded where it is connected to an appliance that is
connected to the appliance grounding conductor of the circuit that supplies that
appliance. (MFGC 310.3)
c. Fittings installed in concealed locations shall be limited to the following types: (MFGC
404.5)
a. Threaded elbows, tees and couplings.
b. Brazed fittings.
c. Welded fittings.
d. Fittings listed to ANSI LC-1/CSA 6.26 or ANSI LC-4.
d. Where gas piping will be concealed within light -frame construction assemblies, the
piping shall be protected against penetration by fasteners in accordance with Sections
404.7.1 through 404.7.3; except black steel piping and galvanized steel piping shall
not be required to be protected. (MFGC 404.7)
e. Gas piping exposed to corrosive action shall be protected in an approved manner.
(MFGC section 404.11)
f. Underground piping systems shall be installed a minimum depth of 12 inches below
grade. Individual underground lines serving outdoor appliances shall be installed a
minimum depth of 8 inches. (MFGC section 404.12)
g. Steel gas piping sizes'/ inch shall be supported at intervals not greater than 6 feet, %
inch and 1 inch shall be supported at intervals of not greater than 8 feet, and piping
sizes 1'/< inch and larger shall be supported at intervals not greater than 10 feet. Refer
to MFGC Table 415.1 of MFGC section 415 for support information for other sizes
and/or materials.
h. Copper gas tubing sizes'/ inch shall be supported at intervals not greater than 4 feet;
% inch and inch shall be supported at intervals of not greater than 6 feet. Refer to
MFGC Table 415.1 of MFGC section 415 for support information for other sizes and/or
materials.
i. Gas piping shall be elevated no less than 3'/ inches above the ground/roof surface
and protected from physical damage. (MFGC section 404.9)
Page 3 of 5
j. A minimum 3-inch sediment trap shall be installed prior to the regulator. If a tee fitting
is used, it shall provide a 90-degree change in direction of gas flow. (MFGC 408.4)
k. Each appliance shall be provided with a shutoff valve in the gas line, separate from
the appliance and no further than 6 feet from the appliance, or located within 50 feet
of the appliance when located at a manifold. (MFGC section 409.5)
I. A readily accessible main shutoff valve with a permanently attached handle shall be
installed in the first available location before the first branch line inside the building.
(MFGC section 409.1.4)
m. Gas piping that serves equipment on the roof of a building shall have a main shutoff
valve located no closer than 10 feet from the roof edge and before the first branch line.
(MMC section 409.1.4 exception)
n. All new gas piping shall be tested and inspected in compliance with MFGC
section 406.
i. Test Pressure: 1% to operating pressure but not less than 26 psig
ii. Duration: thirty (30) minutes
iii. Gauge: 2 psig increments
iv. Test Pressure: Shall be within the middle 60 percent of the gauge
pressure range
o. A final gas piping system, appliance and equipment leakage test shall be
conducted in the presence of the inspector at the final inspection. (MFGC
section 406.6)
p. Shutoff valves installed in tubing systems shall be rigidly and securely supported
independently of the tubing. (MFGC 409.7)
6. Ducts:
a. All joints, longitudinal and transverse seams, and connections in ductwork shall be
securely fastened and sealed. (MMC section 603.9)
b. All duct work shall be hung and supported in compliance with MMC section 603.10
and SMACNA standards, and support spacing shall not exceed 12 feet. Flexible and
other factory -made ducts shall be supported in accordance with the manufacturer's
instructions. (MMC section 603.10)
c. All duct work shall be inspected prior to covering or concealing.
d. All duct insulation shall be inspected prior to covering.
7. Refrigerant Piping:
a. Any portion of a refrigeration system that is subject to physical damage shall be
protected in an approved manner. (MMC section 1101.3)
b. Refrigerant circuit access ports located outdoors shall be fitted with locking -type
tamper -resistant caps or shall be otherwise secured to prevent unauthorized access.
(MMC section 1101.10)
c. Refrigerant piping shall comply with MMC section 1107.
d. Refrigerant piping shall be of an approved material in accordance with MMC section
1107.5.
e. Refrigerant pipe joints erected on the premises shall be exposed to visual inspection
prior to being covered or enclosed. (MMC section 1107.7)
f. Piping insulation shall comply with IECC-12 Table C403.2.8. (MEC C403.2.8)
g. Piping insulation shall be protected from damage, including damage from sunlight,
moisture, equipment maintenance, and wind, and shall provide shielding from solar
radiation to deter degradation of the material. (MEC section C403.2.8.1)
8. Condensate:
Page 4 of 5
a. Condensate from fuel -burning appliances shall discharge to an approved plumbing
fixture via approved corrosion -resistant piping at a minimum slope of 1 % slope. (MMC
section 307.1)
b. Condensate drain systems shall be provided for appliances containing evaporators or
cooling coils. (MMC section 307.2)
c. Condensate drain lines shall not be less than %-inch internal diameter. (MMC section
307.2.2)
9. Indoor Air Quality:
a. Every occupied space shall be ventilated by natural means in accordance with Section
402 or by mechanical ventilation in accordance with MMC Section 403. (MMC 401.2)
b. Mechanical ventilation shall be provided by a method of supply air and return or
exhaust air. The amount of supply air shall be approximately equal to the amount of
return and exhaust air. The system shall not be prohibited from producing negative or
positive pressure. The system to convey ventilation air shall be designed and installed
in accordance with MMC Chapter 6. (MMC 403.1)
If you have any questions or concerns regarding this code review, please contact me via
telephone at 952-442-7520 or e-mail at codereview@mnspect.com. Refer to the permit number
in all correspondences.
Regards,
Nkofe %KaStef n, R.A., NCARB
Plan Reviewer
MNSPECT, LLC
Helping You Comply With The Code
235 First St. W.
Waconia, MN 55367
O: 952-442-7520
F: 952-442-7521
www.mnsr)ect.com
cc: Municipal Property File